UNDR DRAFT or C AIR PRES FAULT
Under Draft or Combustion Air Pressure Fault
Cause: The fan is unable to bring the actual pressure to the CPC-3 set
point.
Solution: Check to see if the VFD displays a fault message. If so, refer to the VFD Fault page. If not, verify the transducer is properly functioning.
NOTE: Transducer sensing tube connections:
TD-2 for Draft = tube on LO, HI left open to room
TD-2 for Sealed Combustion Air = tube on LO, HI left open to room
TD-3 for Open Combustion Air = tube on LO, high left open to room
To verify Transducer voltage is adjusted properly, disconnect sensing
tube from port.
Voltage present across G (positive meter lead) & B (negative meter
lead):
TD-2 = 2.79 VDC
TD-3 = 5.5 VDC
Voltage present across R (positive meter lead) & B (negative meter
lead):
24 VDC on both TD-2 and TD-3