INDUC MECH FAULT
Inducer Mechanical Fault
Cause: The safety circuit between S1 and S2 is open on the VFD.
VSAD: The Motor High Limit or Fan High Limit or tilt Switch is open.
VSUB: The Motor High Limit is open.
Solution: Varies; see below.
VSAD: Check the continuity of the Motor High Limit, Fan High Limit
and Tilt Switch to determine which is open. If there is no
continuity for either of the limits or the switch, contact your
Tjernlund Products Representative for a replacement. If all
have continuity, verify that the wiring between the VFD and
the fan provides continuity. If continuity does not exist
between the VFD and fan, replace the existing wiring.
VSUB: Check the continuity of the Motor High Limit to determine if it
is open. If there is no continuity, contact your Tjernlund
Products Representative for a replacement. If there is
continuity, verify that the wiring between the VFD and the fan
provides continuity. If continuity does not exist between the
VFD and fan, replace the existing wiring.
NOTE: When clearing the Fault History, if "unclearable" appears, ensure you have only the system activated for which you have on site.
i.e. If Combustion Air is activated but no combustion air system is present, the CPC-3 is looking for a safety circuit closure where no safety circuit is present. Deactivate Combustion Air and reset the CPC-3 to allow for Fault History to be cleared.